Building automation for Vocational School Campus BA 1, House II
Building automation for House II of Vocational School Campus BA 1: Each floor is divided into areas, considering fire sections, with each area utilizing an IO node. Hardware design for the IO nodes is based on floor plans and overview plans. Weather data from a weather station will be integrated for weather-appropriate control of blinds; licenses for shading correction and dynamic wind monitoring are required. Lighting control allows up to 3 DALI-EVGs or one DALI group per area, controlled via light switches, DALI presence detectors, or multisensors, with a maximum of 64 DALI-EVGs controllable by one DALI module 753-647. Conventional lighting is also switched via light switches, with one light group per special area. Radiators in some areas are controlled via an actuator using MP-Bus, with temperature sensors for detection. Room temperature controllers in some areas are connected to the nodes via ModbusRTU. Blinds are controlled via blind switches and connected to the IO nodes via blind boxes. Recirculating air cooling units (ULKs) in some rooms can be connected with up to 5 ULKs per node via ModbusRTU. System devices such as controllers are housed in designated sub-distribution boards.